Products : HCD120 10 Ton
HCD120 10 TON The DRY-AIR Stainless Steel HGR Series 120 is built with a 4 Row Field Cleanable Evaporator Coil. This unit is a dual compressor unit, simultaneously rejecting heat to the pool, room and outdoor condenser. This unit can be built vertically in Stainless Steel. (Horizontal is available in non-stainless steel.) Economizer fresh-air purge option available. The available options are air cooled, water cooled and as a ground source geothermal heat pump application. All 1-12 tons come single or three phase.
Refrigerant: R-22, R410A is available Cooling BTU’s: 131,800 (NOMINAL) Compressors: (2) Hermetically Sealed Scroll Unit Capacity @ 50% RH: 54.40 lbs./hr. moisture removal Unit Capacity @ 60% RH: 65.94 lbs./hr. moisture removal Nominal CFM: 4000+
Dimensions
Height: 59.25”
Width: 32.0”
Depth: 39.5”
Water Loop In: 1”
Water Loop Out: 1.5”
Weight: 720 lbs.
Filter Size: 36”x38”
FLS Condenser #206
Electrical Requirements
208-230-1-60 Single Phase
Compressor RLA: 25.3 each
Compressor LRA: 148 each
Fan Motor FLA: 2-4.3*
Fan Motor LRA: 2-10.4*
Total Unit: 59.2
MCA: 70.0
Max. Fuse: 90.0
Controls are 24 Volts off unit.
Supply: Top, Right or Left
Return: Left or Right
Note: Belt Driven Blower Models, call for electrical specs
(Note: Larger blower/belt drive packages can be built into unit or auxiliary blower package added to accommodate additional CFM. Units can be twinned for larger applications.) *These models are dual compressor units and come standard with direct driven twin blowers. Fan motor FLA and RLA shows per each motor. Plumbing is located front left, electrical panel front right, and compressors on bottom right hand side of unit. 36” clearance from front and right hand bottom side required for access and serviceability.